Hi, thanks for this nice addon to read the live data of my Growatt MOD inverter with APX batteries. Few days ago I installed it, adding the addon was really easy.
Sometimes the connection to the inverter is lost and does not comeback again without restarting homeassistant (same restart as after plugin update).
I have setup the connection through USB/Serial (RS485-to-USB adapter) with a generic USB to RS485 adapter with the CH340 chip and set the interval to 30 seconds.
Wondering if this is caused by the USB adapter that I use or is there something we could update in the plugin?
This is visible in the activity section till I restarted home assistant.
Logs:
[33m2026-02-09 06:00:10.099 WARNING (Recorder) [homeassistant.components.sensor.recorder] Entity sensor.growatt_grid_import_energy_today from integration growatt_modbus has state class total_increasing, but its state is not strictly increasing. Triggered by state 2.1 (previous state: 2.2) with last_updated set to 2026-02-09T04:59:49.122874+00:00. Please create a bug report at https://github.com/0xAHA/Growatt_ModbusTCP/issues[0m
[33m2026-02-09 06:00:10.100 WARNING (Recorder) [homeassistant.components.sensor.recorder] Entity sensor.growatt_grid_import_energy_total from integration growatt_modbus has state class total_increasing, but its state is not strictly increasing. Triggered by state 46.8 (previous state: 46.9) with last_updated set to 2026-02-09T04:59:49.122976+00:00. Please create a bug report at https://github.com/0xAHA/Growatt_ModbusTCP/issues[0m
[31m2026-02-09 06:43:12.765 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:43:12.766 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:43:15.775 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:43:15.776 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:43:18.785 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:43:18.785 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:48:12.755 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:48:12.756 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:48:15.764 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:48:15.765 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:48:18.773 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:48:18.774 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:49:21.755 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:49:21.755 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:49:24.765 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:49:24.765 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:49:27.774 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:49:27.774 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:49:57.755 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:49:57.755 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[33m2026-02-09 06:50:00.764 WARNING (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] [MOD TL3-XH Series@/dev/ttyUSB1] 5 consecutive read failures detected - backing off to safe polling interval (1s) to prevent communication errors. This may indicate serial connection issues, low baudrate, or device processing limitations.[0m
[31m2026-02-09 06:50:00.764 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:50:00.764 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:50:03.772 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:50:03.773 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:51:06.755 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:51:06.755 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:51:09.765 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:51:09.765 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:51:12.775 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:51:12.775 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:52:15.755 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:52:15.756 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:52:18.765 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:52:18.765 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:52:21.774 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:52:21.775 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:53:24.755 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:53:24.755 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:53:27.764 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:53:27.765 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:53:30.773 ERROR (SyncWorker_3) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:53:30.773 WARNING (SyncWorker_3) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:54:00.755 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:00.755 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[33m2026-02-09 06:54:03.763 WARNING (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] [MOD TL3-XH Series@/dev/ttyUSB1] 5 consecutive read failures detected - backing off to safe polling interval (1s) to prevent communication errors. This may indicate serial connection issues, low baudrate, or device processing limitations.[0m
[31m2026-02-09 06:54:03.763 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:03.763 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:54:06.772 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:06.772 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:54:36.755 ERROR (SyncWorker_5) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:36.755 WARNING (SyncWorker_5) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:54:39.764 ERROR (SyncWorker_5) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:39.764 WARNING (SyncWorker_5) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:54:42.773 ERROR (SyncWorker_5) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:54:42.773 WARNING (SyncWorker_5) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:55:12.754 ERROR (SyncWorker_1) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:12.755 WARNING (SyncWorker_1) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:55:15.764 ERROR (SyncWorker_1) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:15.764 WARNING (SyncWorker_1) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:55:18.773 ERROR (SyncWorker_1) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:18.773 WARNING (SyncWorker_1) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 06:55:48.755 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:48.755 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 06:55:51.764 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:51.764 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 06:55:54.773 ERROR (SyncWorker_0) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 06:55:54.773 WARNING (SyncWorker_0) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 07:00:54.755 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:00:54.755 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 07:00:57.764 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:00:57.764 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 07:01:00.772 ERROR (SyncWorker_10) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:01:00.773 WARNING (SyncWorker_10) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 07:06:00.755 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:06:00.755 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 07:06:03.765 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:06:03.765 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 07:06:06.774 ERROR (SyncWorker_4) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:06:06.774 WARNING (SyncWorker_4) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 07:11:06.755 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:11:06.756 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 07:11:09.765 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:11:09.765 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 07:11:12.774 ERROR (SyncWorker_8) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:11:12.774 WARNING (SyncWorker_8) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m
[31m2026-02-09 07:16:12.755 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:16:12.756 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 1/3)[0m
[31m2026-02-09 07:16:15.765 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:16:15.765 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 2/3)[0m
[31m2026-02-09 07:16:18.774 ERROR (SyncWorker_9) [custom_components.growatt_modbus.growatt_modbus] Failed to read base input register block[0m
[33m2026-02-09 07:16:18.775 WARNING (SyncWorker_9) [custom_components.growatt_modbus.coordinator] Read returned None (attempt 3/3)[0m