Good evening,
Thank you for this amazing code first of all !!!
The Issue about calculation of ΦHC,nd10 (energy_floorAx10)
Calculate ΦHC,nd,un (unrestricted heating or cooling need to reach the required set-point temperature;
ΦHC,nd,un is positive for heating and negative for cooling).
ΦHC,nd,un = ΦHC,nd10 (θair,set − θair,0)/(θair,10 − θair,0) (C.13)
In code it is needed to have NEGATIVE multiplicator
In case of only positive x10 it returns wrong results
(I checked also by mannual calculation)
My suggestion:
if self.has_heating_demand:
t_air_set = self.t_set_heating
# Set a heating case where the heating load is 10x the floor area (10 W/m2)
energy_floorAx10 = 10 * self.floor_area
elif self.has_cooling_demand:
t_air_set = self.t_set_cooling
energy_floorAx10 = -10 * self.floor_area
else:
raise NameError(
'heating function has been called even though no heating is required')